ValVue Digital Communications Software Ver. 2.80
406
GE Oil & Gas
3. Enter the reading from the milliammeter into the field and click Set (Figure 226).
Figure 226 Setting 4 mA Calibration
ValVue 12400 displays the dialog (Figure 227).
4. Click Yes to confirm setting the 4 mA calibration.
Figure 227 Saving 4 mA Calibration
If the range is outside that shown in Figure 228, an error message appears.
Figure 228 4 mA Calibration Error Message