GE MN-ValVue-v2-8-IOM Manual de Serviço Página 405

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 404
405
4 - 20 mA Calibration
Advanced Setup
4 - 20 mA Calibration
The Calibration Tools window provides the ability to calibrate the 4 - 20 mA source for the AO
signal.
4 mA Calibration
To calibrate Zero at 4 mA:
1. Click on 4 mA as (Figure 224).
Figure 224 Starting 4 mA Calibration
Once 4 mA calibration is started, the 4 mA button grays out.
Figure 225 4 mA Calibration Active
2. Read the value from the precision milliammeter.
Vista de página 404
1 2 ... 400 401 402 403 404 405 406 407 408 409 410 ... 659 660

Comentários a estes Manuais

Sem comentários